Policy for Fire Life Safety Sequence in High Rise Buildings

How can we help?
Search

Policy for Fire Life Safety Sequence in High Rise Buildings

LOS ANGELES FIRE DEPARTMENT

Offical seal for the Los Angeles Fire Department

FIRE PREVENTION BUREAU

POLICY FOR SEQUENCE OF OPERATIONS

Policy: Attached are the guidelines for the Sequence of Operations for Life Safety Systems in High-Rise Buildings. This basic design guideline may vary depending on building requirements. LADBS has been instructed that all systems must be verified by LAFD prior to approval and/or installation. Procedure for Sequence of Operations: 1.0 Basic Guidelines for Sequence of Operations for Life Safety Systems in HighRise Buildings 1.1 Follow the guidelines specific to the requirements for the High-Rise Building in question. 1.2 For any additional questions, contact Unit Commanders.  

BASIC GUIDELINES FOR SEQUENCE OF OPERATIONS FOR LIFE SAFETY SYSTEMS IN HIGH-RISE BUILDINGS The following is a basic design guideline.  Systems may vary depending on building requirements.  All systems should be verified by LAFD prior to approval and/or installation.

Manual Pull Elevator Lobby Smoke Detector Area Smoke/Heat Detectors Duct Smoke Detectors Elevator Shaft Smoke/Heat Detector Sprinkler Water Flow Switch Sprinkler Valve Tamper Switch Special Extingushing Systems Pre-Action Building Power Failure
Annunciate At Fire Control Room (Trouble and Alarm) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Annunciate At 24HR Atteded Remote Location (Trouble and Alarm) Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Activate Audible and Visual Alarm Signals On Floor Of Alarm Yes Yes Yes Yes Yes Yes No Yes Yes No
Shut Down All Air Handling On Floor Of Alarm (HVAC) Yes Yes Yes Yes No Yes No Yes Yes No
Close All Smoke/Fire Dampers On Floor Of Alarm Yes Yes Yes Yes No Yes No Yes Yes Yes
Release All Motorized and Electro-Magnetically Held Doors On Floor Of Alarm Yes Yes Yes Yes No Yes No Yes Yes Yes
Activate Smoke Evacuation System On Floor Of Alarm Yes Yes Yes Yes No Yes No Yes Yes No
Recall All Elevators Serving Floor Of Alarm No Yes No No Yes No No No No Yes
Release All Stair Shaft Door Locks in Building Yes Yes Yes Yes Yes Yes No Yes Yes Yes
Activate All Stair Shaft Pressurization In Building Yes Yes Yes Yes Yes Yes No Yes Yes No
Open Elevator Shaft Smoke/Exhaust Dampers No No No No Yes No No No No No
Release Approved Security Door Locks Yes Yes Yes Yes Yes Yes No Yes Yes Yes
If 24 HR on site monitoring is not provided, an approved automatic dialer system shall be installed and report to a LA City approved 24 HR monitoring company Full Voice-Evac with page by floor capabilities shall be provided for all new high-rise systems. (Rev 4/02)