POLICY FOR SEQUENCE OF OPERATIONS
Policy: Attached are the guidelines for the Sequence of Operations for Life Safety Systems in High-Rise Buildings. This basic design guideline may vary depending on building requirements. LADBS has been instructed that all systems must be verified by LAFD prior to approval and/or installation.
Procedure for Sequence of Operations:
1.0 Basic Guidelines for Sequence of Operations for Life Safety Systems in HighRise Buildings
1.1 Follow the guidelines specific to the requirements for the High-Rise Building in question.
1.2 For any additional questions, contact Unit Commanders.
If 24 HR on site monitoring is not provided, an approved automatic dialer system shall be installed and report to a LA City approved 24 HR monitoring company
Full Voice-Evac with page by floor capabilities shall be provided for all new high-rise systems.
(Rev 4/02)
BASIC GUIDELINES FOR SEQUENCE OF OPERATIONS FOR LIFE SAFETY SYSTEMS IN HIGH-RISE BUILDINGS The following is a basic design guideline. Systems may vary depending on building requirements. All systems should be verified by LAFD prior to approval and/or installation.
Manual Pull | Elevator Lobby Smoke Detector | Area Smoke/Heat Detectors | Duct Smoke Detectors | Elevator Shaft Smoke/Heat Detector | Sprinkler Water Flow Switch | Sprinkler Valve Tamper Switch | Special Extingushing Systems | Pre-Action | Building Power Failure | |
Annunciate At Fire Control Room (Trouble and Alarm) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Annunciate At 24HR Atteded Remote Location (Trouble and Alarm) | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes | Yes |
Activate Audible and Visual Alarm Signals On Floor Of Alarm | Yes | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | No |
Shut Down All Air Handling On Floor Of Alarm (HVAC) | Yes | Yes | Yes | Yes | No | Yes | No | Yes | Yes | No |
Close All Smoke/Fire Dampers On Floor Of Alarm | Yes | Yes | Yes | Yes | No | Yes | No | Yes | Yes | Yes |
Release All Motorized and Electro-Magnetically Held Doors On Floor Of Alarm | Yes | Yes | Yes | Yes | No | Yes | No | Yes | Yes | Yes |
Activate Smoke Evacuation System On Floor Of Alarm | Yes | Yes | Yes | Yes | No | Yes | No | Yes | Yes | No |
Recall All Elevators Serving Floor Of Alarm | No | Yes | No | No | Yes | No | No | No | No | Yes |
Release All Stair Shaft Door Locks in Building | Yes | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | Yes |
Activate All Stair Shaft Pressurization In Building | Yes | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | No |
Open Elevator Shaft Smoke/Exhaust Dampers | No | No | No | No | Yes | No | No | No | No | No |
Release Approved Security Door Locks | Yes | Yes | Yes | Yes | Yes | Yes | No | Yes | Yes | Yes |